Fire Survival Cable Manufacturer, Supplier and Exporter in India

Application:


Fire Survival Cables are required where electrical integrity of the cable has to remain intact for at least three hours, so as to activate and maintain crucial functions such as fire fighting, public announcements, smoke extraction systems, sprinklers, emergency lighting, evacuation path lighting systems etc.

The main applications include places where large number of people congregate for short or limited period of time such as shopping malls, cinema theaters, educational institutions, airport terminals, metro rail networks, high rise office buildings etc. These cables also find use in power generation facilities, petrochemical complexes, nuclear power facilities, mines etc. for phased shut down of the plant and to keep critical functions like communication, rescue and evacuation systems functional during a fire.


Product Construction:

 

Construction - Single / Multi - Cores / Pairs / Traids
Conductor - Solid / Stranded / Flexible  - Annealed Bare  / Tinned Copper Conductor
Fire Barrier - Glass Mica Tape
Insulation - EPR / Silicone Rubber as per IS : 6380
Screening - Individual and / or overall with following options -
- Al-Mylar / Copper Tape with Tinned Copper Drain Wire or
- Braided with Bare / Tinned / Nickel / Silver Plated Copper
Inner Sheath - LSOH / ZHFR or equivalent
Armouring - Galvanized Steel wire helical armouring or wire braiding
Outer Sheath - LSOH / ZHFR or equivalent

 

Reference Standards:

 

BS 7211, BS 7846, BS 7629, BS 8434, BS:6387, IEC:60331.


Technical Data:


Temperature Range : - -15°C to + 180°C
Rated Voltage (Uo/U) :  - 600/1100 V
Test Voltage :  - 3.5kV / 5 min
Bending Radius (Min) : - Upto 8 X cable OD


Features:

 

 

Flammability: IEC 60332-1 & IEC 60332-3 
Resistance to Fire: BS: 6387, IEC 60331 
Smoke Emission: IEC 61034 – 2
Acid Gas Content: IEC 60754 -1 & 2, BS EN 50267 – 1 & 2